Cata-Dyne™ Infrared Oven
Operation and Instructional Manual -
Energy Required
Electrical Requirements
Cata-Dyne™ heaters require electric elements
to pre-heat the catalyst before gas may be applied.
This cycle varies but can take up to 45 minutes per
heater. The preheat current requirements and the power
supply required by the entire system are described in
the customized manual supplied with each oven.
Fuel/Gas Requirements
The main gas pressure must be regulated by the user,
to not exceed the maximum inlet pressure capacity to
the systems mainline regulator.
The mainline pressure regulator must also be adjusted
to supply enough fuel to the system to allow for pressure
drops along the lines, each heater should receive approximately
7 inches w.c. (1.73 kPa) for natural gas or 11 inches
w.c. (2.27 kPa) for propane.
The inlet pressure to the heaters must not exceed
the above mentioned pressure. Above this pressure the
gas may pass through the heater un-reacted,
creating a safety hazard. The minimum inlet pressure
to the heaters is 2 inches w.c. (0.49 kPa) for natural
gas or 3 inches w.c. (0.74 kPa) for propane. Below this,
sufficient fuel to support the catalytic reaction will
not be present and the heater will begin to cool, which
will shut down the entire system.