Terminal Identification
Standard Heater Terminal Connections
Each 4 pin terminal block connects to 2 heaters (refer
to drawings TC_MEAS1, 2, 3 or 4). The top-most and
bottom-most terminal on each block is the power supply
to the pre-amps and should read from 14 VDC to 18 VDC.
Of the two middle terminals, the lower is the lower
number heater, the upper is the higher number heater.
In other words, the signal terminals are the 2 middle
terminals in each 4 wide terminal block and the heater
number increases from the bottom up.
Explosion-Proof Heater Terminal Connections
The thermocouples used for X-proof heater temperature
sensing are dual thermocouples in a single housing.
This redundancy allows detection of problems which could
not be detected using a single thermocouple; specifically
pre-amp, wiring, and multiplexer faults. The control
system reads both thermocouples and must see agreement
within 6.25% or it will shut down the affected zone
of the heating system.
Each 4 pin terminal block connects to a single heater
(refer to drawings TC_MEAS1,2,3 or 4). The top-most
terminal is GND. The next terminal is the power supply
to the dual pre-amp card and should read from 14 VDC
to 18 VDC. The two bottom-most terminals are the signal
pins. The voltage at the signal pins should be within
5% of each other. The heater number increases from
the bottom up.