Lighting Switch Pack (SP-19) Application
Notes
- Quick
Installation Guide
Current
ratings
Fusing
3-Phase Power
Triacs
- Replacing
triacs
Substituting
triacs
- Control inputs
Zero
crossing control
Inductive loads
Matrix cards
Distributers
- Current ratings:
- Calculating the maximum load which can be connected to
a triac box can be a little tricky since there are several
limiting factors involved. The rating on each box will come
down to the rating on each card in the box. Those ratings
are:
-
- 4 Channel Cards:
- Maximum current per channel: 9 Amps (Fuse rated
for 10 amps)
Maximum power per channel: 1000 Watts
Total current per Ch.1&2 or 3&4: 15 Amps
Total power per Ch.1&2 or 3&4: 1800 Watts
- 8 Channel Cards:
- Maximum current per channel: 3.6 Amps (Fuse rated
for 4 amps)
Maximum power per channel: 432 Watts
Total current per Ch.1-4 or 5-8: 15 Amps
Total power per Ch.1-4 or 5-8: 1800 Watts
Note that the total current on the incoming power connector
limits the card to less than the total of the channel ratings.
This connector is rated for 15 Amps at 120 VAC which is
less than the 2 x 10 Amp rating of the two channels. A mix
of different sized loads (e.g. one 9 Amp and one 6 Amp load)
can be used as long as the total does not exceed 15 Amps.
The maximum rating of the SP-19 box is
two 15 Amp circuits per card times four
cards per box for a total of a eight
15 Amp circuits. Keep in mind that the
Canadian electrical code limits the load
on each circuit protected by a 15 Amp
breaker to 80% of 12 Amps.
Back to Topics
-
- Fusing:
- In general, fuses should be rated 20% higher than the
maximum load that is being protected but that can be dropped
to 10% with a slightly higher risk of premature fuse failure.
While the individual channels for a four channel cards are
designed for 10 Amps each, the fuse will fatigue and eventually
fail if run at 10 Amps continuously. The recommended maximum
is therefore 9 Amps which is 10% under the 10 Amp fuse rating.
Similarly, the individual channels of the eight channel
card are fused at 4 Amps, but again the load should not
exceed 3.6 Amps to reduce nuisance blowing.
Back to Topics
-
- 3-Phase Power:
- The SP-19 boxes are rated single phase power only but
two legs of a 208 VAC circuit along with a neutral can be
used as this results in 120 VAC across the load. The simplest
connection is to wire one phase, say phase A to one side
of a card and another phase, say phase B to the other side
of the card. Connect the neutral of the incoming power to
the neutral side of the load using the centre neutral terminals
on the card. This arrangement has the advantage of reduced
neutral current. The same idea can be used on 220/110 VAC
power.
Back to Topics
-
- Triacs:
- Replacing triacs: The
ease of triac replacement is a key feature of the SP-19
triac boxes. The best method to determine triac failure
is to measure the output voltage with a voltmeter. Keep
in mind that the most common failure of triacs is to fail
shorted so that the load never turns off. Triacs may also
fail so that they pass only one half of the AC sine wave.
When a bad channel has been identified:
1. Mark the failed triac with a piece
of tape or felt pen on the tab.
2. Turn off the power at the breaker.
3. Use a robertson screwdriver to remove
the machine screw and hex nut.
4. Slide the triac out of the socket.
5. Apply silicone grease to the new triac.
If there is none available, transfer grease from the failed
triac. Don't get the grease on your clothing - it's tough
to remove.
6. Slide the new triac into the socket,
line up the hole in the tab with the hole in the heat sink,
replace the screw and tighten the nut.
Back to Topics
Substituting triacs:
- Both 4 and 8 channel triac cards use
the same triac which is rated for 15 Amps.
400 V in a TO-220 package with an isolated
tab. Other triacs may be substituted in
a pinch, but they must have an isolated
tab. If there is any question about this,
use an ohmmeter to check for a connection
between the tab and the middle leg of
the triac. If there is continuity, do
not install the triac as there will be
a direct short between the output of the
triac and earth ground. When choosing
a substitute, the voltage rating should
be at least 300V. Triacs with lesser currents
can also be substituted but choose a triac
that is rated for at least 30% more than
the load current. Trinity Electronics
carries a good supply of triacs.
Back to Topics
-
- Control inputs:
- Trinity triac boxes have a buffer card which accepts a
positive DC voltage between 0 and 15 volts. The buffer card,
in turn, applies a +17 VDC, 30 mA signal to the LED side
of the triac optocoupler. A red LED is wired in series to
indicate when a channel is turned on to aid in debugging
systems. A channel is turned on when the control voltage
exceeds the buffer threshold of about 4 volts. The recommended
range is 5 to 15 VDC to turn a channel on and 1 VDC or less
to turn it off.
The buffer cards have been designed to
operate in electrically noisy environments
with long wire runs between the box and
the controller. The input consists of
a 1 Kohm resistor in parallel with 0.1
mfd capacitor to ground. This lower impedance
reduces the sensitivity to the noise pick-up
but this may be too big a load for some
light controllers. If the controller cannot
supply enough current (the maximum would
be 15V/1Kohm=15 mA), the SIP resistors
can be removed. The SIP is a long thin
component with 10 leads which holds all
eight resistors. There are two devices
- one for channels 1 to 8 labelled N1
and the other for channels 9 to 16 labelled
N2. The SIP N1 is located between U1 and
J4 and N2 is between U2 and J5 (see
the buffer card drawing). To remove without
de-soldering, gently wiggle the SIP back
and forth sideways until the leads fatigue
and break off. This produces a clean break
with no shorts between channels. If there
is still too much impedance, the 0.1 mfd
capacitors can also be removed. Use a
pair of lead cutters and cut the lead
flush to the board. Discard the capacitors
as the leads will be too short to re-use.
Remove only as many capacitors as required
to preserve noise immunity for the remaining
channels.
Back to Topics
-
- Zero crossing control:
- Zero crossing control means that the
triac is turned on only when the AC line
voltage passes through zero. The control
signals from most controllers are asynchronous
to the AC sine wave. Since it is not likely
that any channel signal will arrive exactly
at the zero point, the triac is not turned
on until the next zero crossing. This
is sometimes called zero point switching.
A side effect of zero point switching
is a delay of up to one half cycle (8.3
milliseconds) in turning a triac on but
this is imperceptible for all but the
very fastest chase patterns. Triacs only
turn off during zero crossings but that
is due to the nature of a triac and not
the circuitry. Zero point switching is
very desirable when switching resistive
lamp loads because it reduces thermal
shock on the lamp filament which results
when a non-zero voltage is applied to
the filament. With zero point switching,
the filament is gently heated as the sine
wave rises to a peak and then falls to
zero again. The reduced thermal shock
translates into longer lamp life.
The zero crossing feature in Trinity's triac cards is incorporated
into the triac opto-couplers. The MOC 3030 and the MOC 3031
optocouplers have zero crossing control built in whereas
the MOC 3010 and MOC 3011 do not. The later devices turn
on when the channel voltage goes high regardless of the
instantaneous value of the line voltage. The parts ending
in 1 (3031 and 3011) require less LED current than the parts
ending in zero (3030 and 3110) but both can be used interchangeably
in the Trinity triac cards. As explained below, non-zero
crossing controlled optocouplers should be used for inductive
loads such as lamps with built-in transformers.
Back to Topics
-
- Inductive loads:
- Inductive loads pose a problem for lighting control. Inductive
loads incorporate coiled wire as part of their circuitry
such as motors or transformers. In the lighting industry,
the most common inductive loads are light fixtures with
low voltage transformers built into the base. The first
problem that inductive loads present is the phase shift
between voltage and current. If the inductance is too high,
a triac cannot turn off even when there is no gate drive.
Trinity's triac cards incorporate snubber circuits so that
the triacs operate reliably on most inductive loads.
-
- The second problem results when the drive signals create
a situation where the triac turns on for
an odd number of half cycles. A triac
must be triggered at the beginning of
both the positive going half of a sine
wave and the negative going half. Under
certain conditions, the triac will be
repetitively turned on for 3, 5, 7, or
9 half cycles in a row. The extra positive
or negative half cycle effectively create
a DC component in the transformer primary
winding. This creates overheating which
can burn open the winding. The problem
is generally created through the use of
the zero crossing control circuitry which
turns on triacs for complete half cycles.
This problem can be solved in two ways:
- Use a controller with integral cycle
control which triggers the triac for an equal number of
positive and negative half cycles.
- Use non-zero crossing optocouplers
(MOC 3010 or MOC 3011) in the triac cards.
-
- Some companies request only non-zero crossing optocouplers
so that all triac boxes that they stock are suitable for
transformer based lighting without having to check which
components were used. The trade off is reduced life for
standard resistive lamps.
Back to Topics
-
- Matrix cards:
- Matrix operation is a very simple but effective chasing
arrangement. Lamps are arranged in a square of four columns
and four rows. In X mode, the row triacs will chase with
the four channel pattern and all the column triacs will
be turned on steady.
In Y mode, the column triacs will chase and the four row
triacs will be turned on. Like any four channel switching,
lamps can be paralleled to 8, 12 or 16 rows and columns
but the chase is still four channel. Both X and Y triacs
can be turned on at the same time but there is a certain
amount of ghosting which occurs when current finds a "sneak
path" through several lamps in series. The result is
a pattern of bright lights and several other lamps glowing
with partial intensity. This mode looks good but may also
appear to an installer like a partially failed triac.
-
- Trinity has developed inexpensive matrix cards which provide
switching for four hots and four lamp returns (effectively
the lamp neutrals but to avoid approval problems we don't
use that term). Most applications will use two 4-channel
cards - one card for switching the four hots and one for
switching the four returns. The matrix card is very small
and mounts in place of one of the 8-channel buffer chips
on the buffer card. This will leave 8-channels of buffering
for an additional matrix or more basic switching. The matrix
cards require four chasing signals plus two additional lines:
Y mode and X+Y mode (inputs 5 and 6 have no function - see
the 16 channel buffer card drawing). With no signal present,
the matrix defaults to X mode. When a control signal is
applied to the Y mode line, the switching converts to Y
mode. The X+Y mode chases both rows and columns simultaneously
with the aforementioned ghosting effect. If both Y and X+Y
lines are high, the Y mode will take priority. As with the
other inputs, the recommended control voltages are 5 to
15 VDC. In most cases, a box can be retrofit for matrix
operation in the field by installing one or more matrix
cards and rewiring the triac cards.
Back to Topics
-
- Distributers:
- Allstar Show Industries Inc.
http://www.allstar-show.com
allsales@allstar-show.com
Axe Music
http://www.axemusic.com
edmontonmanager@axemusic.com
Back to Topics
|
|
|
home
| services
| products
| tech
notes | clients
| contact
| site
map & search
All email enquiries of any sort are welcomed... Please click:
Trinity Electronics Systems Ltd. Edmonton, Alberta, Canada
- custom electronics design and manufacturing.
|